GLBS-12/24 kV Load Break Switch
1. Brief Introduction
The GLBS is a SF6 load break switch which relies on the chemical properties of SF6 for insulation and arc-quenching. It is a 12-24 kV medium voltage load break switch is designed for applications with indoor and outdoor medium voltage switchgear panels. It consists of a three position rotary switch mechanism mounted and sealed within an epoxy gas tank charged with SF6 gas. It is available as a line switch (AL or BL) or a fuse-switch (BF) with fuse-holders as well as an operating mechanism with tripping capability. Terminals connecting to cables and bus-bars can be of the cone-shaped variety for accommodating silicone bushings on the cable or bus-bar system. Motor operation is optional for the GLBS.
2. The GLBS had the following features:
1. High load breaking capacity (transfer current or maximum breaking capacity of 2600 A)
2. Large creepage distance and superior insulation properties
3. Arc proof and tested for internal arcing
4. Maintenance free or low maintenance requirements
5. Compact dimensions
6. Rugged design ensures long mechanical and electric life
7. Low gas pressure system requiring less than 1kg of SF6 per switch
3. Technical parameters of GLBS/AL, GLBS/BL has the following parameters
1. Rated voltage: 12/24kv
2. Withstand voltage to earth and between poles: 28/50kV
3. Withstand voltage across insolating distance: 32/60 kV
4. Impulse withstand voltage to earth and between poles: 75/125kV
5. Impulse withstand voltage across insolating distance: 85/145kV
6. Rated frequency: 50/60 Hz
7. Rated current: 630 A
8. Rated short-time current (Ik)
Tk=1s systems: 25 kA
Tk=3s systems: 20 kA (choice)
9. Making current: 50 kA
10. Electric endurance: 500 times
11. Mechanical endurance: 5000 times
12. Temperature:
Panel including: Auxiliary instruments and relays: -40-70
Panel excluding: Auxiliary instruments and relays: -5-55
13. Rated SF6 gas pressure (20): ??10 kPa
4. Technical parameters of GLBS/BF has the following parameters
1. Rated voltage: 12/24kv
2. Withstand voltage to earth and between poles: 28/50kV
3. Withstand voltage across insolating distance: 32/60 kV
4. Impulse withstand voltage to earth and between poles: 75/125kV
5. Impulse withstand voltage across insolating distance: 85/145kV
6. Rated frequency: 50/60 Hz
7. Rated current: 630 A
8. Rated short-time current (Ik)
Tk=1s systems: 25 kA
Tk=3s systems: 20 kA (choice)
9. Making current: 50 kA
10. Max. Breaking capacity (transfer current): 2600 A
11. Rated short-circuit breaking current (fuse): 31.5 kA
12. Electric endurance: 500 times
13. Mechanical endurance: 5000 times
14. Temperature:
Panel including: Auxiliary instruments and relays: -40-70
Panel excluding: Auxiliary instruments and relays: -5-55
15. Rated SF6 gas pressure (20): ??10 kPa
5. Standard
1. IEC 129 (earthing switch)
2. IEC265 (load break switch)
3. IEC420 (load break switch+fuse)
More Product Features
Load Break Switch (GLBS 12/24 kV SF6)